This website uses cookies primarily for visitor analytics. Certain pages will ask you to fill in contact details to receive additional information. On these pages you have the option of having the site log your details for future visits. Indicating you want the site to remember your details will place a cookie on your device. To view our full cookie policy, please click here. You can also view it at any time by going to our Contact Us page.

BROWSE PRODUCTS
 

Fire Prevention - Have you specified the right type of RCD?

Government statistics indicate that changes to Fire Safety Regulations and associated regulations e. g. IEE Regs Ch. 42, have resulted in a reduction in the number of fires (circa 32,000 in 2001/02 to 20,000 2009/10 in non-domestic buildings). Reducing the risk of fire in Commercial and Public Buildings is an obvious area of focus for the design of electrical installations ¹.

Electrical fires can be caused by relatively low values of earth leakage current², a few hundred milliamps depending on location and surrounding conditions if not interrupted quickly, can produce ignition. Keeping earth leakage currents within safe limits with the demands for increased comfort (HVAC), back up for IT systems (UPS), improved EMC (harmonic filters) and surge protection (Type 1 & 2 devices), all add to the complexity of designing a secure electrical supply - ref IEE Regs 314, whilst retaining electrical safety. Areas associated with the Public and Non Technical Staff which include electrical supplies with complex loads i.e. HVAC, Lighting, illumination level control, IT systems with UPS back up (Olympic stadiums would make a classic case study for designers), are particularly difficult to deal with safely. This requires a clear understanding of the associated risks, removal or reduction of the risk through other means, supported by the appropriate safety case and documentation. Where part of safety case (risk reduction) for the installation relies on automatic disconnection of the supply using RCDs, circuits containing power electronics e.g. Inverters and UPS, need to be segregated from circuits containing AC or A type RCD's and protected by their own B type RCCD³ - reference EN 50178 & IEE Wiring Regs. Ch 33.  

The reason; equipment containing power electronics can under certain conditions, produce DC fault currents within the AC network, which will interfere with the operation of afore mentioned devices. B Type RCD's are designed to sense DC earth leakage currents as well as high frequency AC leakage currents, which are also generated as a result of PWM and the associated filters (required to meet EMC regulations)- especially within  lower cost solutions. 
From a design and specification point of view these leakage currents can be significant across the complete frequency spectrum. If we take an inverter as an example to select the RCD protection, there has to be a clear understanding of the leakage current characteristics across the frequency range of the inverter output; leakage current at 50Hz, maximum leakage current plus the frequency that it is generated at, leakage current at the maximum frequency - your inverter manufacturer has this information as it is required for their EMC test validation.

This information will enable the specification and selection of appropriate protective devices, and reduce the risk of so called "nuisance trips"4 i.e. the RCD is probably doing what it was designed to do!  Undefined or unclear operating conditions within a technical specification requiring automatic disconnection, at best could be embarrassing at a public event for The Consultants and Main Contractors, or worse if it creates additional risk for the Public - Dangerous! If you would like more detailed information relating to this subject, Doepke UK have a free 60 page Technical Application guide available on request or information on Type B, A or AC RCDs (email sales@doepke.co.uk).

Notes 
1:  UK Statistics Authority Nov 2010 /Reported results indicate that: 20% of fires were attributed to electricity - electrical equipment/appliances (13%) and electrical distribution (7%).  
2:  Earth leakage - A natural phenomena normally associated with small values of current flowing/ tracking to earth from a live cable or appliance. These values are additive within an installation.
3:   AC and A type RCDs rely on the change in the magnetising effect of AC current for trip coil. DC current flowing in the circuit saturates the trip coil reducing the sensitivity or preventing tripping completely. B Type RCD's have additional sensing circuits, designed to detect dc earth leakage currents. 
4: The term "nuisance trip" is often applied when there is a lack of understanding about what is actually happening within the electrical installation: For some additional reading on this subject see www.marcspages.co.uk